2002-02-27 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT CS MINIMUM FACILITIES CALL FOR
 1 W/C & 1 LAV MALE - 2 W/C'S & 2 LAV'S
 FEMALE. ALSO 1 DRINKING FOUNTAIN REQUIR-
 ED. SPC TABLE 407 & SEC 407.1.3.
 2) SHT A-2 SHOW CLEAR FLOOR SPACE FOR
 ALL HDCP FIXTURES. LAV'S, W/C'S, DRINK-
 ING FOUNTAIN, AND BREAK ROOM SINK.
 3) SHT A-5 DETAIL #6, PLEASE SHOW COMP-
 LIANCE WITH FACBC SEC 4.24 AND ALL SUB-
 SECTIONS.
 4) SHT A-5 SHOW DETAIL OF DRINKING FOUN-
 TAIN. COMPLY WITH FACBC SEC 4.15 AND ALL
 SUBSECTIONS, AND SEC 4.1.3(10) FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 5) SHT PM-1 PLEASE SUBMIT MANUFACTURE'S
 INFORMATION ON INSTANTANIOUS W/HEATERS.
 SHOW LISTING FOR PRODUCT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377