 PLANS REVIEWED UNDER THE 2001 FLORIDA
 BUILDING CODE, MECHANICAL
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PROVIDE LOCATION OF OU-1.PLEASE
 NOTE AS PER 2001 FBC, MECH 306.5 -
 EQUIPMENT REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16
 FEET, AN APPROVED PERMANENT MEANS OF
 ACCESS IS REQUIRED.
  
 2.PROVIDE INFORMATION AS TO WHAT WILL
 BE KEPT IN THE "STORAGE" SPACE.
  
 3.SEE ELECTRICAL PLAN REVIEW COMMENT
 #3.
  
 PLEASE NOTE, AS PER 2001 FBC, MECHANICAL
 401.5, OUTSIDE AIR EXHAUST & INTAKE
 OPENINGS SHALL BE LOCTED A MINUMUM OF
 10 FT FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT.401.5.2, EXHAUST
 OPENINGS SHALL NOT BE DIRECTED ONTO
 WALKWAYS.
  