| 2002-02-26 00:00:00 | ******************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS |
| | NEED TO BE SHOWN. WATTS PER SQ FT, 180VA |
| | PER OUTLET, 220-3,220-11,220-11,220-13, |
| | PLEASE ALSO NOTE THAT ALL CONTINUOUS |
| | LOADS NEED TO BE SHOWN AT 125%. |
| | 215-2/3,230-42. |
| | |
| | 2)NOTE: PLEASE NOTE THAT A/C SYSTEM IS |
| | SHOWN BEING FED FROM ANOTHER SERVICE |
| | THAT FEED ANOTHER SPACE. PLEASE NOTE, |
| | THIS IS NOT PERMITTED. |
| | SYSTEM NEEDS TO COME FROM THE SAME |
| | SERVICE AS EACH TENANT SPACE. 230-72, |
| | 230-2 ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4)NOTE: PLEASE NOTE THAT INSTANT WATER |
| | HEATER IS SHOWN AS SINGLE PHASE 120V |
| | ON E-2 AND PANEL SCHEDUE AS 3-PHASE? |
| | PLEASE CLARIFY. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING OUTLET(S) |
| | FOR "SHOW" WINDOWS. 210-62. |
| | |
| | 6)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT |
| | PER 600-5. NOTE #8 ON E-1 NEEDS TO BE |
| | SHOWN. |
| | |
| | 7)NOTE: PLEASE NOTE LOAD CALCS FOR TRACK |
| | LIGHTING NEEDS TO BE SHOWN. 220-12B. |
| | |
| | 8)NOTE: PLEASE NOTE THAT PANEL IS SHOWN |
| | IN A STORAGE ROOM. PLEASE NOTE ON PLANS |
| | THAT AREA MUST MEET 110-26 AND OUTLINED |
| | MARKINGS ARE TO PAINTED ON FLOORS TO |
| | SHOW CLEARENCE REQ`MENTS.110-26 AND |
| | NOTE, 384-7. |
| | |
| | 9)NOTE: PLEASE NOTE THAT NOTE #2 UNDER |
| | WIRE AND CABLE ON E-3. MENTIONS COLOR |
| | CODING PER NEC. |
| | PLEASE NOTE THAT PER LOCAL AMENDMENTS, |
| | 215-8 |
| | 120/208V, BLK/RED/BLUE AND 277/480V |
| | BROWN/PURPLE/YELLOW. |
| | PLEASE NOTE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |