| Plan Review Notes For Permit 02020780 |
| Permit Number |
02020780 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-18 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLANS SHALL BE ROUTED TO THE PALM | | | BEACH COUNTY HEALTH UNIT, DIVISION OF | | | ENVIRONMENTAL HEALTH, 901 EVERNIA ST | | | WPB (561) 355-3018 EXT 1134 | | | 2) SHT A2.51 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR URNAL. (30"X48") | | | 3) SHT A2.51 URNAL HEIGHT SHALL BE 17" | | | PER 4.18.2. PLEASE SHOW ON TOILET ELEV- | | | ATION5/A2.51. | | | 4) SHT P2.51 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTO SHALL BE LOCATED NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" NOT AT | | | THE TOP OF THE DROP AS SHOWN. PDI WH-201 | | | AND MANUFACTURES INSTALLATION INSTRUCT- | | | IONS. | | | 5) SHT P2.51 WATER RISER DIAGRAM, A | | | BACKFLOW PREVENTER IS REQUIRED ON WATER | | | SERVICE FOR POOL BATH BLDG. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|