Plan Review Notes
Plan Review Notes For Permit 02020780
Permit Number 02020780
Review Stop P
Sequence Number 1
Notes
Date Text
2002-09-18 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, DIVISION OF
 ENVIRONMENTAL HEALTH, 901 EVERNIA ST
 WPB (561) 355-3018 EXT 1134
 2) SHT A2.51 PLEASE SHOW CLEAR FLOOR
 SPACE FOR URNAL. (30"X48")
 3) SHT A2.51 URNAL HEIGHT SHALL BE 17"
 PER 4.18.2. PLEASE SHOW ON TOILET ELEV-
 ATION5/A2.51.
 4) SHT P2.51 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTO SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF THE DROP AS SHOWN. PDI WH-201
 AND MANUFACTURES INSTALLATION INSTRUCT-
 IONS.
 5) SHT P2.51 WATER RISER DIAGRAM, A
 BACKFLOW PREVENTER IS REQUIRED ON WATER
 SERVICE FOR POOL BATH BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377