| Plan Review Notes For Permit 02020716 |
| Permit Number |
02020716 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-11 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) THE WRONG EDITION OF THE CODE IS | | | LISTED IN THE GENERAL CONSTRUCTION NOTES | | | ON SHEET A.3. 1997 STANDARD BUILDING | | | CODE IS THE PROPER EDITION. PLEASE | | | CORRECT. | | | | | | 2)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ROOF COVERING MATERIAL | | | | | | 3) PROVIDE MANUFACTURERS SPECIFICATIONS | | | AND LISTING INFORMATION FOR BBQ. A | | | SEPARATE PERMIT WILL BE REQUIRED FOR | | | GAS. | | | | | | 4) PROVIDE SOIL TEST REPORTPER SECTION | | | 1804.2.2 OF CITY AMENDMENTS TO 1997 SBC. | | | | | | 5) THE STRUCTURE IS LOCATED IN AN A5 | | | FLOOD ZONE THE FLOOR IS REQUIRED TO BE | | | ELEVATED TO 6" ABOVE BASE FLOOD | | | ELEVATION. PLEASE INDICATE THE PROPER | | | FLOOR ELEVATION ON THE PLANS.(MIN. 7'6" | | | N.G.V.D.) NOTE: AN ELEVATION CERTIFICATE | | | WILL BE REQUIRED. | | | | | | 6)PROVIDE TWO COPIES OF A RECENT SURVEY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|