2002-03-11 00:00:00*************BUILDING UNSAT*************
  
 1) THE WRONG EDITION OF THE CODE IS
 LISTED IN THE GENERAL CONSTRUCTION NOTES
 ON SHEET A.3. 1997 STANDARD BUILDING
 CODE IS THE PROPER EDITION. PLEASE
 CORRECT.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOF COVERING MATERIAL
  
 3) PROVIDE MANUFACTURERS SPECIFICATIONS
 AND LISTING INFORMATION FOR BBQ. A
 SEPARATE PERMIT WILL BE REQUIRED FOR
 GAS.
  
 4) PROVIDE SOIL TEST REPORTPER SECTION
 1804.2.2 OF CITY AMENDMENTS TO 1997 SBC.
  
 5) THE STRUCTURE IS LOCATED IN AN A5
 FLOOD ZONE THE FLOOR IS REQUIRED TO BE
 ELEVATED TO 6" ABOVE BASE FLOOD
 ELEVATION. PLEASE INDICATE THE PROPER
 FLOOR ELEVATION ON THE PLANS.(MIN. 7'6"
 N.G.V.D.) NOTE: AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 6)PROVIDE TWO COPIES OF A RECENT SURVEY.
  