| 2002-02-20 00:00:00 | *******************DENIED*************** | | | | | | | | | APPLICATION INDICATES TENANT SEPARATION, | | | SHOW COMPLIANCE WITH FLA ENERGY CODE | | | (1997), THE SUPPLY OF HEATING & COOLING | | | TO EACH ZONE SHALL BE CONTROLLED BY | | | INDIVIDUAL THERMOSTATIC CONTROLS FOR | | | CONTROLLING THE TEMPERATURE WITHIN THE | | | ZONE. | | | | | | INDICATE THE USE OF THE ROOM TO THE | | | SOUTHEAST.NO VENTILATION PROVIDED FOR | | | THIS SPACE.ELECTIRICAL PLAN INDICATES | | | AN OUTLET FOR TELEPHONE & COMPUTER. | | | | | | PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|