| 2002-02-22 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) UNTIL MARCH 1, 2002 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED.NEITHER CODE IS |
| | REFERENCED ON THE PLANS.STATE WHICH |
| | CODE THE WORK IS TO BE CONSTRUCTED TO. |
| | |
| | 2) AMEND THE PLANS TO SHOW THE |
| | USE/OCCUPANCY OF EACH ROOM. |
| | |
| | 3) THE PROJECT DESCRIPTION ON THE PERMIT |
| | APPLICATION FORM STATES "TENANT |
| | SEPARATION WALLS", BUT THE NEW WALLS ON |
| | THE PLANS ARE ANNOTATED AS "NEW INTERIOR |
| | PARTITION",AND THERE ARE INTERCONNECTING |
| | DOORS BETWEEN ROOMS EAST OF THE ELEVATOR |
| | ANNOTATE THE PLANS TO CLARIFY THE SCOPE |
| | OF THE PERMIT APPLICATION. |
| | |
| | 4) FBC 1005.4EVERY SLEEPING ROOM SHALL |
| | HAVE AT LEAST ONE EXTERIOR EMERGENCY |
| | ESCAPE AND RESCUE OPENING.IDENTIFY THE |
| | BEDROOMS ON THE PLANS AND DEMONSTRATE |
| | COMPLIANCE.THE INTERNAL DOOR HARDWARE |
| | SHALL NOT BE LOCKABLE, PREVENTING ACCESS |
| | TO THE EXISTING EXIT DOOR. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |