| Plan Review Notes For Permit 02020700 |
| Permit Number |
02020700 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-14 00:00:00 | 1) "EXHAUST DUCT DISCHARGE POINT SHALL | | | BE AT LEAST 6 FEET FROM ANY EXTERIOR | | | WALL OR ROOF".RE: NFPA 1, SECTION | | | 17-3.5.4. | | | 2) "NO SMOKING OR OPEN FLAMES" IN LARGE | | | LETTERS ON A CONTRASTING BACKGROUND | | | SHALL BE INSTALLED IN ALL SPRAY AREAS | | | AND PAINT STORAGE ROOMS".RE: NFPA 1, | | | SECTION 17-3.8.8. | | | 3) THE SPRAY BOOTH SHALL BE ELECTRICALLY | | | GROUNDED AND BONDED".RE: NFPA 1, SECTION | | | 17-3.4.5. | | | 4) ELECTRICAL EQUIPMENT AND APPURTENANT | | | EQUIPMENT TO COMPLY WITH NFPA 1, SECTION | | | 17-3.4.1. | | | 5) PORTABLE FIRE EXTINGUISHERS | | | REQUIRED. RE: NFPA 1, SECTION 17-3.7.6. | | | 6) SIGNED AND SEALED LEGAL SURVEY | | | REQUIRED OR A LEASE AGREEMENT WITH | | | RAILROAD FOR USE OF RAILROAD EASEMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|