Plan Review Notes
Plan Review Notes For Permit 02020700
Permit Number 02020700
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-14 00:00:001) "EXHAUST DUCT DISCHARGE POINT SHALL
 BE AT LEAST 6 FEET FROM ANY EXTERIOR
 WALL OR ROOF".RE: NFPA 1, SECTION
 17-3.5.4.
 2) "NO SMOKING OR OPEN FLAMES" IN LARGE
 LETTERS ON A CONTRASTING BACKGROUND
 SHALL BE INSTALLED IN ALL SPRAY AREAS
 AND PAINT STORAGE ROOMS".RE: NFPA 1,
 SECTION 17-3.8.8.
 3) THE SPRAY BOOTH SHALL BE ELECTRICALLY
 GROUNDED AND BONDED".RE: NFPA 1, SECTION
 17-3.4.5.
 4) ELECTRICAL EQUIPMENT AND APPURTENANT
 EQUIPMENT TO COMPLY WITH NFPA 1, SECTION
 17-3.4.1.
 5) PORTABLE FIRE EXTINGUISHERS
 REQUIRED. RE: NFPA 1, SECTION 17-3.7.6.
 6) SIGNED AND SEALED LEGAL SURVEY
 REQUIRED OR A LEASE AGREEMENT WITH
 RAILROAD FOR USE OF RAILROAD EASEMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910