| Plan Review Notes For Permit 02020700 |
| Permit Number |
02020700 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-21 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | REFER TO MECHANICAL AND FIRE REVIEW | | | COMMENTS ALSO. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) UNTIL MARCH 1, 2002 EITHER STANDARD | | | BUILDING CODE 1997 OR FLORIDA BUILDING | | | CODE 2001 MAY BE USED.NEITHER CODE IS | | | REFERENCED ON THE PLANS.STATE WHICH | | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | | | 2) ANNOTATE THE PLANS TO STATE THE USE/ | | | OCCUPANCY OF THE MAIN TENANT 3 AREA | | | AROUND THE SPRAY BOOTH. | | | | | | 3) TABLE 704.1THE OCCUPANCY SEPARATION | | | WALL TO 'TENANT 2' SHALL HAVE A TWO-HOUR | | | FIRE-RATING.THIS REQUIREMENT STANDS | | | WHETHER 'TENANT 3' IS CONSIDERED | | | FACTORY-INDUSTRIAL OR HAZARDOUS (SUB- | | | CLASSIFICATION H3, SEE FBC TABLE 308.2C) | | | AMEND THE PLANS TO DEMONSTRATE | | | COMPLIANCE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|