2002-02-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 REFER TO MECHANICAL AND FIRE REVIEW
 COMMENTS ALSO.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) ANNOTATE THE PLANS TO STATE THE USE/
 OCCUPANCY OF THE MAIN TENANT 3 AREA
 AROUND THE SPRAY BOOTH.
  
 3) TABLE 704.1THE OCCUPANCY SEPARATION
 WALL TO 'TENANT 2' SHALL HAVE A TWO-HOUR
 FIRE-RATING.THIS REQUIREMENT STANDS
 WHETHER 'TENANT 3' IS CONSIDERED
 FACTORY-INDUSTRIAL OR HAZARDOUS (SUB-
 CLASSIFICATION H3, SEE FBC TABLE 308.2C)
 AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS