| Plan Review Notes For Permit 02020683 |
| Permit Number |
02020683 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-01 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | -ED. PLEASE NOTE MAIN/BRKRS AND PANELS | | | ARE TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENTPER 110-9. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | MISSING BLDG/FOOTER STEEL. | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 5)NOTE: PLEASE NOTE MISSING HALL OUTLET | | | PER 210-52H | | | | | | 6)NOTE: PLEASE NOTE THAT AS OF JAN 1ST, | | | 2002 NEC. ART 210-12. PLEASE LIST THE | | | ARC FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULES. | | | | | | 7)NOTE: PLEASE CLARIFY NOTE THAT MENTION | | | -S 99 NEC AND STATE CODE? PLEASE NOTE | | | THAT WE ARE UNDER 99 NEC AND OUR LOCAL | | | AMENDMENTS BUT THERE IS NO STATE | | | ELECTRICAL CODE THAT WE ARE AWARE OF? | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|