| Notes |
| Date |
Text |
| 2002-02-20 00:00:00 | ********************DENIED************** | | | | | | | | | 1.INDICATE DUCT SIZE OF NEW R6 DUCT- | | | BOARD. | | | | | | 2.INDICATE ANY EXISTING FIRE DAMPERS. | | | | | | 3.PROVIDE INFORMATION ON ANY DUCT | | | SMOKE DETECTORS IN AREAS USED FOR | | | EGRESS. | | | | | | 4.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|