| Notes |
| Date |
Text |
| 2002-02-26 00:00:00 | | | | | | | 1.PLAN SHEET M-1 OUTSIDE AIR CALCS., | | | A. CALCULATION DOES NOT INCLUDE | | | KITCHEN AREA AS REQUIRED PER | | | TABLE 403.3. | | | NOTE-PLAN SHEETS A5.01 - A5.06 STILL | | | REFER TO THE 1997 SBC FOR THE DOORS | | | & WINDOWS. | | | | | | 2.BALANCED AIR RETURN - DEMONSTRATE A | | | 3/4" UNDERCUT OF A DOOR COMPLIES | | | WITH 601.4 OF THE 2001 FMC IN WHICH | | | PRESSURE DIFFERENTIAL ACROSS DOORS | | | SHALL BE LIMITED TO 0.001" WC OR | | | LESS. | | | | | | 3.PLAN SHEET M-6 INDICATES AUXILIARY | | | DRAIN PAN WITH OVERFLOW PROTECTION | | | ON THE UPPER FLOORS ONLY.AS PER | | | 2001 FLORIDA BUILDING CODE, MECH | | | 307.2.3,ALL COILS ON WHICH | | | CONDENSATION WILL OCCUR SHALL HAVE | | | AN AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|