| Plan Review Notes For Permit 02020594 |
| Permit Number |
02020594 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-07 00:00:00 | A) THE REQUIRED FIRE ALARM SYSTEM ARE TO | | | BE PERMITTED SEPARATELY. PLANS, CUT | | | SHEETS, WIRING DIAGRAMS, AND BATTERY | | | CALCULATIONS ARE TO BE PROVIDED. MANUAL | | | PULL STATIONS AND HORN STROBES ARE TO | | | BE PROVIDED THROUGHOUT THE BUILDING. ON | | | 3.1.02 WRITER CONTACTED FELIX SIERRA | | | WH ADVISED THAT THE FIRE ALARM CONTROL | | | PANEL WILL BE LOCATED IN AN EXTERIOR | | | STORAGE ROOM. THE FIRE ALARM SYSTEM | | | IS TO BE CLASS A OR FULLY ADDRESSABLE. | | | B) THE EXIT STAIRS ARE TO BE AT LEAST | | | 36" WIDE SINCE OCCUPANT LOADS ARE | | | EXPECTED TO BE LESS THAN 50 PERSONS. | | | THE MINIMUM HEIGHT OF RISER SHALL BE | | | 4", MAXIMUM HEIGHT OF RISER 7", WITH | | | THE MINIMUM TREAD DEPTH OF AT LEAST | | | 11"S. | | | C) ILLUMINATION IS TO BE PROVIDED FOR | | | THE MEANS OF EGRESS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|