| Plan Review Notes For Permit 02020594 |
| Permit Number |
02020594 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | | | | THE BUILDING WAS REVIEWED UNDER THE | | | FLORIDA FIRE PREVENTION CODE. | | | 1) FIRE HYDRANTS WILL BE RELOCATED TO | | | ISLANDS TO PREVENT PROBLEMS WITH ACCESS | | | TO THEM. THIS ARRANGEMENT WAS AGREED TO | | | BY MR. FELIX SIERRA. | | | 2) GENERAL NOTES SECTION SHOULD READ | | | FLORIDA FIRE PREVENTION CODE. | | | 3) ALL STORAGE ROOMS OUTSIDE OF DWELLING | | | UNITS TO BE PROTECTED BY AT LEASAT ONE | | | HOUR FIRE SEPARATION OF FIRE SPRINKLERS. | | | 4) THE REQUIREMENT FOR A FIRE ALARM | | | SYSTEM STILL SEEMS TO BE PRESENT. THE | | | TWO EXCEPTIONS TO THIS CODE REQUIREMENT | | | DOES NOT APPEAR TO APPLY. PLEASE REVIEW | | | CODE REQUIREMENT AND EXCEPTIONS. | | | 5) THE INFORMATION PROVIDED FOR THE | | | WINDOWS IS CONFUSING. ARE THE EGRESS | | | WINDOWS, SELF-CLOSING. PLEASE PROVIDE | | | ADDITIONAL DETAILS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096, EXT. 8497 | | | 835-2910 |
|