| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | | | | BUILDING:H. PISKURA | | | | | | FBC 705.1.3, REQUIRES THE FIRE RATED | | | WINDOWS, (AND DOORS), TO BE LABELED AND | | | LISTED IN ACCORDANCE WITH NFPA 80-95. | | | | | | THE STORAGE ROOM DOORS SHOWN AS (9) ON | | | THE PLAN ARE REQUIRED TO BE RATED [45 | | | MIN] SINCE THEY ARE WITHIN THE TEN FEET | | | WIDE SHADOW OF PROTECTION REQUIRED BY | | | FBC 1006.2.4. |
|