Plan Review Notes
Plan Review Notes For Permit 02020541
Permit Number 02020541
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-13 00:00:00****************PROVISO!****************
 PLEASE NOTE: THIS SERVICE REQUIRES A #4
 GROUNDING ELECTRODE CONDUCTOR AS PER
 250-66.INSTALL SAME.
 ALSO NOTE TWO GROUND RODS MAY BE
 REQUIRED AS PER250-50(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT.8392


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved