2002-03-06 00:00:00PLUMBING PLAN REVIEW, FBC 2001,DENIED.
 (1) GENERAL NOTES #1 THE CURRENT CODE IS
 FBC 2001, SEC 424.2.6 ENGINEERING DESIGN
 NOT SBCCI-94 PBC SWIMMINGPOOL CODE.
 (2) NOTE #5 DISPOSAL OF WATER. SEE FBC
 2001, SEC 424.2.10 WASTE WATER DISPOSAL.
 (3) NOTE #7 WATER SUPPLY. SEE FBC 2001
 SEC 424.2.9 WATER SUPPLY, AND LOCAL ORD.
 #2853-95 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVICE.
 (4) SEC 424.2.13.2 JOINTS, CONNECTIONS.
 PURPLE PRIMER REQUIRED ON PVC PIPING,
 FBC 2001 PLUMBING SEC 605.21
 (5A) COMPLY WITH FBC 2001,SEC 104.2
 BUILDING DRAWINGS, SPECIFICATIONS.
 TO MANY SWIMMING POOL PIPING SCHEMATICS,
 ON THE PLANS, THIS IS VERY CONFUSING,
 SHOW INDIVIDUAL PIPING SCHEMATIC FOR EA.
 SWIMMING POOL,SPA. SHOW PIPING FOR THE
 ENTIRE SYSTEM, PIPE SIZES,VENTS, SUCTION
 AND DISCHARGE PIPING,ECT.
 (5B) PROVIDE A COPY OF CONTRACT,MATERIAL
 FURNISHED IS VAGUE,IN WHAT IS INCLUDED
 FOR THIS JOB.