| 2002-02-20 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | UNTIL MARCH 1, 2001 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED.AS NEITHER CODE |
| | IS REFERENCED ON THE PLANS, THEY HAVE |
| | BEEN REVIEWED FOR COMPLIANCE WITH |
| | FLORIDA BUILDING CODE 2001. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC 704.1.1THE LENGTH OF PARTITION |
| | BETWEEN THE STAIR WALL AND THE EXISTING |
| | DOOR TO THE EAST OF THE EAST STAIR IS |
| | NOT SHOWN AS ONE-HOUR FIRE-RATED.THIS |
| | IS NOW AN OCCUPANCY SEPARATION WALL. |
| | AMEND THE PLANS TO SHOW THE REQUIREMENT |
| | FOR A ONE-HOUR FIRE-RATED PARTITION. |
| | |
| | 3) FBC 1004FILLING IN THE DOOR IN THE |
| | IN THE WALL TO THE EAST OF THE EAST |
| | STAIR RESULTS IN THE TENANCY EAST OF THE |
| | EAST STAIR BECOMING INDEPENDENT OF |
| | SUITE 400.AMEND THE PLANS TO SHOW THAT |
| | THE MEANS OF EGRESS FROM THE TENANCY IS |
| | FULLY COMPLIANT NOW THAT EGRESS THROUGH |
| | SUITE 400 IS NO LONGER AVAILABLE. |
| | |
| | 4) FBC 1004.1.4THE EXIT DOORS FROM |
| | SUITE 400 ARE NOT REMOTE.THE DISTANCE |
| | BETWEEN THE DOORS SHALL BE NOT LESS THAN |
| | THE HALF THE MAXIMUM OVERALL DIMENSION |
| | OF THE AREA SERVED.AMEND THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 5) FBC 2405.2THE GLAZING IN THE |
| | SIDELITE ADJACENT THE NEW SUITE 400 |
| | ENTRANCE DOOR IS IN A 'HAZARDOUS |
| | LOCATION' AND IS REQUIRED TO BE SAFETY |
| | GLASS SATISFYING THE REQUIREMENTS OF THE |
| | CONSUMER PRODUCT SAFETY COMMISSION 16, |
| | CODE OF FEDERAL REGULATIONS, PART 1201 |
| | (CPSC 16-CFR, PART 1201).SUBMIT |
| | DETAILS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 6) FBC 11-4.1.3(12)(A)SHEET 1, 'A.D.A |
| | CLEARNCES'.THE MAXIMUM HEIGHT OF |
| | ACCESSIBLE SHELVING AND RAILS IS SHOWN |
| | AS 54".THIS SHOULD READ 48" MAX AS |
| | SHOWN IN FIGURE 38. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |