| Plan Review Notes For Permit 02020493 |
| Permit Number |
02020493 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) BACKFLOW REQUIRED FOR CONSTRUCTION | | | 2) IF UNITS ARE NOT INDIVIDUALLY METERED | | | THEN THE BACKFLOW WILL HAVE TO STAY. | | | 3) IF IRRIGATION WORK IS DONE A SEPARATE | | | PERMIT SHALL BE REQUIRED. PLUMBING CON- | | | TRACTOR SHALL INSTALL VALVE AND WATTS | | | N36 VACUUM BREAKER FOR IRRIGATION. | | | 4) PLEASE SHOW LOCATION OF FLOOR DRAIN | | | IN LAUNDRY ROOM. | | | 5) PLEASE SUBMIT A SANITARY RISER DIA- | | | GRAM FOR ALL UNITS AND LAUNDRY ROOM. | | | 6) SHT P-2 WATER HEATER DETAIL, FUNNEL | | | FLOOR DRAIN NOT APPROVED. FLOOR SINK RE- | | | QUIRED FOR ALL INDIRECT WASTE. WATER | | | HEATER IN LAUNDRY ROOM DOES NOT REQUIRE | | | AN EMERGENCY DRAIN PAN AND T/P RELIEF | | | LINE CAN DRAIN OUTSIDE BLDG 6" ABOVE | | | GRADE. | | | 7) SHT A-4 DETAIL (2) SHOWS 1'0" TO SEAT | | | OF W/C. STANDARD HEIGHT IS 1'5". | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|