Notes
Date Text
2002-02-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) BACKFLOW REQUIRED FOR CONSTRUCTION
 2) IF UNITS ARE NOT INDIVIDUALLY METERED
 THEN THE BACKFLOW WILL HAVE TO STAY.
 3) IF IRRIGATION WORK IS DONE A SEPARATE
 PERMIT SHALL BE REQUIRED. PLUMBING CON-
 TRACTOR SHALL INSTALL VALVE AND WATTS
 N36 VACUUM BREAKER FOR IRRIGATION.
 4) PLEASE SHOW LOCATION OF FLOOR DRAIN
 IN LAUNDRY ROOM.
 5) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM FOR ALL UNITS AND LAUNDRY ROOM.
 6) SHT P-2 WATER HEATER DETAIL, FUNNEL
 FLOOR DRAIN NOT APPROVED. FLOOR SINK RE-
 QUIRED FOR ALL INDIRECT WASTE. WATER
 HEATER IN LAUNDRY ROOM DOES NOT REQUIRE
 AN EMERGENCY DRAIN PAN AND T/P RELIEF
 LINE CAN DRAIN OUTSIDE BLDG 6" ABOVE
 GRADE.
 7) SHT A-4 DETAIL (2) SHOWS 1'0" TO SEAT
 OF W/C. STANDARD HEIGHT IS 1'5".
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377