Plan Review Notes
Plan Review Notes For Permit 02020493
Permit Number 02020493
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-14 00:00:00******************** UNSAT ***********
  
 1)NOTE: PLEASE CALRIFY OCP FOR AHU.
 PLEASE SEE E-1 &-2 SHOW 60 FUSES?
 PANELIS SHOWING 40A.
  
 2)NOTE: PLEASE NOTE MISSING OUTLETS TO
 MEET 210-52.
  
 3)NOTE: PLEASE CLARIFY IF ALL
 CONTINUOUSLOADS ARE AT 125% IN HOUSE
 PANEL?
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 KITCHEN COUNTERSPACE PER 210-52C-1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. PLANS WOULD HAVE BEEN
 REDLINED, BUT WERE COMING BACK FOR
 OTHERCOMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372