| Plan Review Notes For Permit 02020493 |
| Permit Number |
02020493 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-14 00:00:00 | ******************** UNSAT *********** | | | | | | 1)NOTE: PLEASE CALRIFY OCP FOR AHU. | | | PLEASE SEE E-1 &-2 SHOW 60 FUSES? | | | PANELIS SHOWING 40A. | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLETS TO | | | MEET 210-52. | | | | | | 3)NOTE: PLEASE CLARIFY IF ALL | | | CONTINUOUSLOADS ARE AT 125% IN HOUSE | | | PANEL? | | | | | | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | KITCHEN COUNTERSPACE PER 210-52C-1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. PLANS WOULD HAVE BEEN | | | REDLINED, BUT WERE COMING BACK FOR | | | OTHERCOMMENTS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|