| 2002-03-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY |
| | AMEND)FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) UNTIL MARCH 1, 2002 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED.NEITHER CODE IS |
| | REFERENCED ON THE PLANS.STATE ON THE |
| | PLANS WHICH CODE IS TO BE USED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 4) FL ENERGY CODE 101.1.2 AND 103.0 |
| | THE ADDITION SHALL COMPLY WITH FLORIDA |
| | ENERGY CODE.SUBMIT ENERGY CODE |
| | COMPLIANCE FORMS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 5) SBC 1501INSUFFICIENT ROOF COVERING |
| | INFORMATION WAS SUBMITTED AT THE TIME OF |
| | APPLICATION.A SEPARATE ROOFING PERMIT |
| | APPLICATION IS REQUIRED. |
| | |
| | 6) SBC* 1606.4THE SUBMITTED PRODUCT |
| | CONTROL NOTICES OF ACCEPTANCE FOR THE |
| | WINDOW AND GLASS SLIDING DOOR ARE |
| | EXPIRED AND THE ASSOCIATED DRAWINGS FOR |
| | THE GLASS SLIDING DOOR ARE MISSING. |
| | SUBMIT CURRENT AND COMPLETE PRODUCT |
| | APPROVALS. |
| | |
| | 7) SBC 2308PROVIDE DETAILS OF THE |
| | MEANS OF ATTACHMENT OF THE NEW WALLS TO |
| | THE EXISTING BUILDING.ALSO, THE |
| | PLYWOOD SHEATHING ON THE ADDITION SHALL |
| | BE MIN. 5/8" THICK (SEE |
| | SBC TABLE 2308.2.2B) |
| | |
| | 8) SBC 1804.1THE BASE OF THE FOOTERS |
| | SHALL BE MIN. 12" BELOW FINISHED GRADE. |
| | ANNOTATE THE PLANS TO SHOW COMPLIANCE. |
| | |
| | 9) SBC 2303.1THE GROUND AROUND THE |
| | BUILDING SHALL BE GRADED TO SLOPE AWAY |
| | FROM IT.ANNOTATE THE PLANS TO SHOW |
| | COMPLIANCE. |
| | |
| | 10) SBC 1909.1WHAT IS THE THICKNESS OF |
| | THE FLOOR SLAB?ALSO, THE PROPOSED |
| | RECESS IN THE TOP OF THE SLAB TO |
| | ACCOMMODATE THE WALL SOLE PLATE IS NOT |
| | NECESSARY.IT WILL REDUCE THE CONCRETE |
| | COVER TO THE REINFORCEMENT AND IS NOT |
| | RECOMMENDED. |
| | |
| | 11) SBC 1909.2A VAPOR RETARDER OF 6MIL |
| | (MINIMUM) POLYTHENE OR OTHER APPROVED |
| | MATERIAL SHALL BE INSTALLED UNDERNEATH |
| | THE SLAB.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 12) SBC* 2304.1.2TERMITE TREATMENT OF |
| | SOIL UNDER AND AROUND THE SLAB AND |
| | FOOTINGS IS REQUIRED.ANNOTATE THE |
| | PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 13) SBC* 2304.2.5LATH AND STUCCO. |
| | ANNOTATE THE PLANS TO SHOW AN APPROVED |
| | WEEP SCREED (STUCCO STOP) PLACED NOT |
| | LESS THAN 6" ABOVE FINISHED GRADE TO |
| | TERMINATE THE STUCCO AT THE BASE OF THE |
| | WALL. |
| | |
| | 14) ANNOTATE THE PLANS TO SHOW THE SIZE |
| | OF THE J-BOLT BETWEEN THE WALL SOLE |
| | PLATE AND FOOTINGS. |
| | |
| | 15) ANNOTATE THE PLANS TO SHOW THAT ALL |
| | FRAMING AND SHEATHING IS THE BE |
| | PRESERVATIVE TREATED WOOD. |
| | |
| | 16) SBC 2308.3.2 THE WINDOW AND DOOR |
| | HEADERS SHALL BE SUPPORTED BY A JACK |
| | STUD AT EACH END IN ACCORDANCE WITH |
| | TABLE 2308.3A.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 17) SBC 1606.1.1WIND FORCES.CONFIRM |
| | THE BASIS OF DESIGN FOR RESISTANCE TO |
| | WIND LOAD AND STATE THE BASIC VELOCITY |
| | PRESSURE. |
| | |
| | 18) SBC 1503.1.2.3WALL SECTION.IF |
| | THE ROOF COVERING IS NOT OF A TYPE |
| | RECOGNIZED AS 'WATER RETAINING', THE |
| | MINIMUM SLOPE OF 1/4 INCH/FT (INCREASED |
| | AS NECESSARY TO ACCOUNT FOR DEFLECTION) |
| | AND THE DIRECTION OF SLOPE SHALL BE |
| | SHOWN. |
| | |
| | 19) SBC 2309.7.2THE FLAT ROOF VOID |
| | SHALL BE VENTILATED BY A NETT AREA OF |
| | OPENING NOT LESS THAN 1/250 OF THE AREA |
| | OF THE CEILING BELOW.ANNOTATE THE |
| | PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |