2002-02-11 00:00:00********************UNSAT!**************
 PLEASE PROVIDE THE FOLLOWING AND
 RESUBMIT:
  
 1) A.I.C. RATING AT FIST MEANS OF
 DISCONNECT,AS PER 110-9 & 110-10.
  
 2) LOAD CALCULATIONS AS PER 215-5.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561) 659-8096 EXT.8392