Plan Review Notes
Plan Review Notes For Permit 02020324
Permit Number 02020324
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHT 5 CHEMICAL STORAGE ROOM, 4" FLOOR
 DRAIN SHALL DRAIN TO SANITARY.
 2) SHT 5 ALL WASTE TO DRAIN TO SANITARY
 AND OVERFLOW SHALL DRAIN TO STORM OR
 DRAIN FIELD.
 3) SHT 5 POOL WASTE DETAIL & NOTE #9,
 ALL WASTE TO SANITARY AND OVERFLOW TO
 STORM.
 4) SHT 5 CHLOLRINE ROOMS SHALL HAVE: CON
 TINUOUS FORCED DRAFT VENTILATION 64E-9.
 007(16)(A)1.A.
 5) SHT 5 EB TO DRAIN INDIRECTLY TO FLOOR
 SINK LOCATED NEAR EQUIPMENT SO PIPING
 DOES NOT RUN ACROSS FLOOR. FLOOR DRAIN
 SHOWN BUT FLOOR SINK REQUIRED.
 6) PLEASE SUBMIT POOL HEATER MANUFACTURE
 SHEET FOR REVIEW. MUST SHOW BTU'S AND
 APPROVING AGENCY, (LISTING AGENCY).
 7) PLEASE SUBMIT MSDS FOR CHEMICALS USED
 FOR POOLS.
 8) MENS ROOM IN MASTER PLAN (01030147)
 DO NOT SHOW URNAL. 64E-9.006(2)(F)1, SEE
 CHART.
 9) CHLORINE ROOM DOOR SHALL OPEN OUT AND
 SHALL NOT BE LOCATED ADJACENT TO THE
 FILTER ROOM ENTRANCE. 64E-9.007(16)(A)(1
 )A
  
 REVEIW BY KEN STEVENS
 (561) 659-8096 EXT 8377