1 |
|
| Notes |
| Date |
Text |
| 2002-02-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 | | | | | | 1) SHT 5 CHEMICAL STORAGE ROOM, 4" FLOOR | | | DRAIN SHALL DRAIN TO SANITARY. | | | 2) SHT 5 ALL WASTE TO DRAIN TO SANITARY | | | AND OVERFLOW SHALL DRAIN TO STORM OR | | | DRAIN FIELD. | | | 3) SHT 5 POOL WASTE DETAIL & NOTE #9, | | | ALL WASTE TO SANITARY AND OVERFLOW TO | | | STORM. | | | 4) SHT 5 CHLOLRINE ROOMS SHALL HAVE: CON | | | TINUOUS FORCED DRAFT VENTILATION 64E-9. | | | 007(16)(A)1.A. | | | 5) SHT 5 EB TO DRAIN INDIRECTLY TO FLOOR | | | SINK LOCATED NEAR EQUIPMENT SO PIPING | | | DOES NOT RUN ACROSS FLOOR. FLOOR DRAIN | | | SHOWN BUT FLOOR SINK REQUIRED. | | | 6) PLEASE SUBMIT POOL HEATER MANUFACTURE | | | SHEET FOR REVIEW. MUST SHOW BTU'S AND | | | APPROVING AGENCY, (LISTING AGENCY). | | | 7) PLEASE SUBMIT MSDS FOR CHEMICALS USED | | | FOR POOLS. | | | 8) MENS ROOM IN MASTER PLAN (01030147) | | | DO NOT SHOW URNAL. 64E-9.006(2)(F)1, SEE | | | CHART. | | | 9) CHLORINE ROOM DOOR SHALL OPEN OUT AND | | | SHALL NOT BE LOCATED ADJACENT TO THE | | | FILTER ROOM ENTRANCE. 64E-9.007(16)(A)(1 | | | )A | | | | | | REVEIW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|