Plan Review Notes
Plan Review Notes For Permit 02020240
Permit Number 02020240
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHTS A1-1/A7-1 DETAIL #3 SINK TO COM-
 PLY WITH FACBC SEC 4.24. SHOW DETAILS.
 2) SHT A1-1 MINIMUM FACILITIES REQUIRE
 2 MALE AND 2 FEMALE WATER CLOSETS AND
 LAVS. BLDG "A" SPC TABLE 407
 3) SHT A1-1 MINIMUM FACILITIES REQUIRE
 1 MALE AND 2 FEMALE WATER CLOSETS AND
 LAVS. BLDG "B" SPC TABLE 407
 4) SHT A1-1 MINIMUM FACILITIES REQUIRE
 ONE DRINKING FOUNTAIN. IF DRINKING FOUN-
 TAINS ARE NOT HI/LOW THEN PROVISIONS
 SHALL BE MADE FOR THOSE WHO HAVE DIFFI-
 CULTY BENDING OR STOOPING. FACBC SEC
 4.1.3(10)
 5) SHTS A1-1/A7-1 DETAIL #8 SINK TO COM-
 PLY WITH FACBC SEC 4.24 SHOW DETAILS.
 6) SHTS A1-1/A7-2 DETAIL #17 SINK TO
 COMPLY WITH FACBC SEC 4.24. SHOW DETAILS
 7) SHT P-4 WATER HEATER DETAIL, DIELECT-
 RIC UNIONS NOT APPROVED FOR USE IN WATER
 SYSTEM. THESE ARE GAS FITTINGS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377