| Plan Review Notes For Permit 02020240 |
| Permit Number |
02020240 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-25 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHTS A1-1/A7-1 DETAIL #3 SINK TO COM- | | | PLY WITH FACBC SEC 4.24. SHOW DETAILS. | | | 2) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | 2 MALE AND 2 FEMALE WATER CLOSETS AND | | | LAVS. BLDG "A" SPC TABLE 407 | | | 3) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | 1 MALE AND 2 FEMALE WATER CLOSETS AND | | | LAVS. BLDG "B" SPC TABLE 407 | | | 4) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | ONE DRINKING FOUNTAIN. IF DRINKING FOUN- | | | TAINS ARE NOT HI/LOW THEN PROVISIONS | | | SHALL BE MADE FOR THOSE WHO HAVE DIFFI- | | | CULTY BENDING OR STOOPING. FACBC SEC | | | 4.1.3(10) | | | 5) SHTS A1-1/A7-1 DETAIL #8 SINK TO COM- | | | PLY WITH FACBC SEC 4.24 SHOW DETAILS. | | | 6) SHTS A1-1/A7-2 DETAIL #17 SINK TO | | | COMPLY WITH FACBC SEC 4.24. SHOW DETAILS | | | 7) SHT P-4 WATER HEATER DETAIL, DIELECT- | | | RIC UNIONS NOT APPROVED FOR USE IN WATER | | | SYSTEM. THESE ARE GAS FITTINGS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|