| 2002-04-11 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | FOR FOUNDATION PERMIT |
| | 1) PER PREVIOUS REVIEW: SUBMIT CALCULAT- |
| | IONS FOR MINIMUM FACILITIES PER SPC TAB. |
| | 407 AND SEC. 407.1.3. CALCULATIONS SUB- |
| | MITTED NOT CLEAR. MULTIPLE OCCUPANCY - |
| | SHOW MIN. FAC FOR EACH OCCUPANCY. |
| | 2) PER PREVIOUS REVIEW: SUBMIT STORM |
| | RISER DIAGRAM. INDICATE HOW STORM PIPING |
| | WILL BE RUN. WILL IT BE IN SLAB? |
| | |
| | --FOR BLDG PERMIT-- |
| | 3) PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH COUNTY HEALTH UNIT, DIVISION OF |
| | ENVIRONMENTAL HEALTH. 901 EVERNIA STREET |
| | WPB FLA 33401. THIS SHALL BE DONE BEFORE |
| | RESUBMITTING FOR PLAN REVIEW. |
| | 4) GREASE LINE SHOWS NEW LINE TO MEZZ. |
| | THIS NEW LINE SHALL RUN TO SANITARY. |
| | 5) HAND SINKS IN KITCHEN DO NOT NEED TO |
| | BE INDIRECTLY DRAINED. PREVIOUS COMMENT |
| | #6, I DID NOT KNOW THEY WERE HAND SINKS. |
| | 6) SHTS P-1/P-2 SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT FLOOR PLAN. |
| | A) DRINKING FOUNTAINS BY MENS AND WOMEN |
| | REST ROOMS NOT ON RISER DIAGRAM. |
| | B) ARTS & CRAFTS TAKEN OFF BEFORE MENS |
| | ROOM ON FLOOR PLAN BUT NOT ON RISER DIA. |
| | C) OFFICE BATH ROOM TAKEN OFF AFTER |
| | DRAIN LINE TURNS TO MENS ROOM NOT REFLEC |
| | TED ON RISER DIAGRAM. |
| | 7) GREASE TRAP SHALL BE SIZED BY RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE (561) |
| | 837-4074. (SEE ATTACHED SHEET FOR APPRO- |
| | VED GREASE TRAP DETAIL) |
| | 8) SHOWER BATH BY DANCE CLASS SHALL BE |
| | ACCESSIBLE PER FACBC-SEC 4.1.3(11) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |