| Plan Review Notes For Permit 02020214 |
| Permit Number |
02020214 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-11 00:00:00 | | | | DENIED: | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.MANUFACTURER SUBMITTAL DATA FOR THE | | | FIRE MASTER FAST WRAP. | | | | | | 2.NOTE #7 IN THE "GENERAL NOTES", 3 | | | FT VERTICAL SEPARATION IN NFPA 96 | | | IS FOR AIR INTAKE ONLY.10 FT | | | CLEARANCE IS REQUIRED FROM ANY | | | ADJACENT BUILDING, PARKING AREAS, | | | AND ADJACENT PROPERTY LINES. | | | | | | 3.FRESH AIR INTAKE SHALL BE SCREENED | | | WITH CORROSION RESISTANT MATERIAL AS | | | PER 1997 SMC 405. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|