| Plan Review Notes For Permit 02020158 |
| Permit Number |
02020158 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-11 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE MISSING EGRESS | | | LIGHTING PER 210-70. NO CONTROL FOR | | | CEILING FAN? | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE: PLEASE NOTE THAT BATH REC NEEDS | | | TO BE SHOWN AS GFI.210-8 | | | | | | PLEASE MAKE THE ABOVE CHANGES AND SUBMIT | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|