Plan Review Notes
Plan Review Notes For Permit 02020138
Permit Number 02020138
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-11 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IS THE 200A PANEL NOTED NEW?
  
 2)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING THE NEW SERVICE AND GROUNDING
 DETAIL.
  
 3)NOTE: PLEASE NOTE THAT TWO PANEL
 SCHEDULE WERE SUBMITTED? BOTH DO NOT
 CORRELATE. PLEASE NOTE THAT FIRST ONE
 SHOWS GARAGE? PLEASE SHOW DETAIL FOR
 THE FEED TO THAT GARAGE. DETACHED???
  
 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 THAT SAYS LOAD CALCULATIONS,,,,PLEASE
 NOTE THAT THERE ARE NO LOAD CALCS
 SHOWN.
  
 7) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE DRAW IN SWITCH LEGS FOR ALL
 LIGHTING SWITCHES.
  
 8)NOTE: PLEASE SHOW WIRE SIZES ON PANEL
 SCHEDULES.
  
 9)NOTE: PLEASE NOTE THAT OUTLET SPACING
 ALONG KITCHEN COUNTERSPACE NEEDS TO
 MEET 210-52-C-1
  
 10)NOTE: PLEASE NOTE THAT BATH RECEPTS
 NEED TO BE SHOWN AS GFI. 210-8
  
  
 11)NOTE: PLEASE CLARIFY LOCATION OF
 PANEL AND HOW FEED IS COMING INTO HOUSE?
 PLEASE NOTE THAT PANEL IS SHOWN IN UTIL-
 -ITY ROOM AND DOES NOT MEET 110-26 FOR
 CLEARENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.\\
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW