| 2002-02-11 00:00:00 | ******************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | IS THE 200A PANEL NOTED NEW? |
| | |
| | 2)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| | SHOWING THE NEW SERVICE AND GROUNDING |
| | DETAIL. |
| | |
| | 3)NOTE: PLEASE NOTE THAT TWO PANEL |
| | SCHEDULE WERE SUBMITTED? BOTH DO NOT |
| | CORRELATE. PLEASE NOTE THAT FIRST ONE |
| | SHOWS GARAGE? PLEASE SHOW DETAIL FOR |
| | THE FEED TO THAT GARAGE. DETACHED??? |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| | THAT SAYS LOAD CALCULATIONS,,,,PLEASE |
| | NOTE THAT THERE ARE NO LOAD CALCS |
| | SHOWN. |
| | |
| | 7) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE DRAW IN SWITCH LEGS FOR ALL |
| | LIGHTING SWITCHES. |
| | |
| | 8)NOTE: PLEASE SHOW WIRE SIZES ON PANEL |
| | SCHEDULES. |
| | |
| | 9)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| | ALONG KITCHEN COUNTERSPACE NEEDS TO |
| | MEET 210-52-C-1 |
| | |
| | 10)NOTE: PLEASE NOTE THAT BATH RECEPTS |
| | NEED TO BE SHOWN AS GFI. 210-8 |
| | |
| | |
| | 11)NOTE: PLEASE CLARIFY LOCATION OF |
| | PANEL AND HOW FEED IS COMING INTO HOUSE? |
| | PLEASE NOTE THAT PANEL IS SHOWN IN UTIL- |
| | -ITY ROOM AND DOES NOT MEET 110-26 FOR |
| | CLEARENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL.\\ |
| | |