| 2002-02-06 00:00:00 | ****************PROVISO!**************** | | | PLEASE NOTE AND CORRECT THE FOLLOWING BE | | | FORE CALLING INSPECTION: | | | 1) PROVIDE A.I.C. RATING. | | | | | | 2) COMPLY WITH 230-28 WHEN INSTALLING RI | | | ER. | | | | | | 3) IDENTIFY FEEDER CONDUCTORS AS PER 215 | | | -8,CITY AND COUNTY AMMENDMENTS. | | | | | | 4) ELIMINATE THE #6 GROUNDING CONDUCTOR | | | FROM MAIN DISCONNECT TO PREVENT PARALLEL | | | PATHS.USE ONLY THE ONE FROM THE METER E | | | NCLOSURE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT.8392 |
|