2002-02-06 00:00:00*****************PROVISO****************
 PLEASE NOTE AND COMPLY WITH THE
 FOLLOWING BEFORE CALLING INSPECTION:
  
 1) PROVIDE A.I.C. RATINGS AS PER 110-9 &
 110-10.
  
 2) RISER AS PER 230-28.
  
 3) FEEDER CONDUCTORS IDENTIFIED AS PER
 215-8 CITY AMMENDMENTS.(SEE NOTES ON
 PLAN.)
  
 4) REMOVE #6 GROUNDING ELECTRODE
 CONDUCTOR FROM MAIN DISCONNECT,USE ONLY
 THE ONE FROM THE METER ENCLOSURE TO
 PREVENT PARALLEL PATHS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392