| Plan Review Notes For Permit 02020133 |
| Permit Number |
02020133 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | *****************PROVISO**************** | | | PLEASE NOTE AND COMPLY WITH THE | | | FOLLOWING BEFORE CALLING INSPECTION: | | | | | | 1) PROVIDE A.I.C. RATINGS AS PER 110-9 & | | | 110-10. | | | | | | 2) RISER AS PER 230-28. | | | | | | 3) FEEDER CONDUCTORS IDENTIFIED AS PER | | | 215-8 CITY AMMENDMENTS.(SEE NOTES ON | | | PLAN.) | | | | | | 4) REMOVE #6 GROUNDING ELECTRODE | | | CONDUCTOR FROM MAIN DISCONNECT,USE ONLY | | | THE ONE FROM THE METER ENCLOSURE TO | | | PREVENT PARALLEL PATHS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT.8392 |
|