| Plan Review Notes For Permit 02020085 |
| Permit Number |
02020085 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2003-01-02 00:00:00 | UNSAT! | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE REVISION SHEET NUMBERS DO NOT | | | CORRELATE WITH THE PERMITED SET. | | | | | | THE RECEPTACLE SPACING IN THE BREAKFAST | | | & FAMILY ROOMS DO NOT MEET THE | | | REQUIREMENTS OF 210-52(A)(1),SEE | | | REVIEWED PLAN. | | | | | | THE FEEDERS ON THE RISER DIAGRAM ARE | | | INCORRECTLY MARKED(REVERSED). | | | | | | PLEASE MAKE NECESSARY CORRECTIONS AND | | | RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|