| Plan Review Notes For Permit 02020081 |
| Permit Number |
02020081 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-26 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION PER 210-12 | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSING DINING ROOM. | | | | | | 5)NOTE: PLEASE NOTE THAT GFI FOR A/C | | | COND UNIT IS SHOWN AS OPTIONAL? PLEASE | | | NOTE THAT THE GFI OUTLET IS REQ`D PER | | | MECH CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|