| Plan Review Notes For Permit 02011677 |
| Permit Number |
02011677 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-04 00:00:00 | ****************DENIED!***************** | | | 1) ONLY ONE SERVICE DROP PERMITTED AS | | | PER 230-2. | | | | | | 2) NO A.I.C. RATINGS PROVIDED. | | | | | | 3) GROUNDING ELECTRODE CONDUCTOR AS PER | | | 250-66. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561) 659-8096 | | | EXT.8392 |
|