Plan Review Notes
Plan Review Notes For Permit 02011641
Permit Number 02011641
Review Stop M
Sequence Number 1
Notes
Date Text
2002-02-14 00:00:00 
  
 INDICATE ON PLANS WHICH CODE THE PLANS
 ARE DESIGNED TO.
 1997 STANDARD BUILDING CODEOR
 2001 FLORIDA BUILDING CODE
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 2.PLAN SHEET 9 LEGEND INDICATES
 EXISTING WATER COOLED HEAT PUMPS.
 AC-2 LOOKS TO BE A NEW HEAT PUMP.
 PROVIDE MANUFACTURER INFORMATION FOR
 ANY NEW EQUIPMENT BEING INSTALLED.
  
 3.INDICATE CONDENSTATE LINE AND
 TERMINATION POINT ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.