| Plan Review Notes For Permit 02011641 |
| Permit Number |
02011641 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-14 00:00:00 | | | | | | | INDICATE ON PLANS WHICH CODE THE PLANS | | | ARE DESIGNED TO. | | | 1997 STANDARD BUILDING CODEOR | | | 2001 FLORIDA BUILDING CODE | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 2.PLAN SHEET 9 LEGEND INDICATES | | | EXISTING WATER COOLED HEAT PUMPS. | | | AC-2 LOOKS TO BE A NEW HEAT PUMP. | | | PROVIDE MANUFACTURER INFORMATION FOR | | | ANY NEW EQUIPMENT BEING INSTALLED. | | | | | | 3.INDICATE CONDENSTATE LINE AND | | | TERMINATION POINT ON THE PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|