| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SEALED BY THE ENGINEER OF RECORD. | | | 471.025 | | | | | | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR EXIT AND EMERGENCY LIGHTING. | | | | | | 3)NOTE: PLEASE CLARIFY CONDUCTOR SIZES | | | FOR "NOTE 4" ON RISER NOTES. | | | | | | 4)NOTE: PLEASE CLARIFY GROUNDING FOR | | | TRANSFORMER 250-24 ,,, | | | | | | 5)NOTE: PLEASE NOTE THAT MEANS OF | | | DISCONNECT FOR TRANSFORMER ABOVE CEILING | | | MUST MEET 110-26. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|