| Plan Review Notes For Permit 02011641 |
| Permit Number |
02011641 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FL ENERGY CODE = FLORIDA ENERGY | | | EFFICIENCY CODE FOR BUILD'G CONSTR'N | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) UNTIL MARCH 1, 2002 EITHER STANDARD | | | BUILDING CODE 1997 OR FLORIDA BUILDING | | | CODE 2001 MAY BE USED.NEITHER CODE IS | | | REFERENCED ON THE PLANS.STATE WHICH | | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | | | 3) FL ACC CODE 4.1.3(12)(A)SHEET 1, | | | 'A.D.A CLEARANCES'.THE MAXIMUM HEIGHT | | | OF ACCESSIBLE SHELVING AND RAILS IS | | | SHOWN AS 54".THIS SHOULD READ 48" MAX, | | | AS SHOWN ON FIGURE 38. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|