| Plan Review Notes For Permit 02011628 |
| Permit Number |
02011628 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-08-27 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} CIRCUITS S2-2,4 & 6 ON SHEET E-1 2ND | | | FLOOR ELECTRIC PLAN AREN'T LISTED ON | | | SAMECIRCUITS ON THE PANEL SCHEDULE. | | | | | | 2} PANEL S2 SHOWN AS REVISION #4WAS NOT | | | ON REV #4. | | | | | | 3} LOCATION OF S2 NOT SHOWN ON THE PLANS | | | | | | 4}PLEASE CORRELATE THE REVISION NUMBERS | | | WITH REVISIONS THAT WERE MADE. | | | | | | 5} THE RISER DIAGRAM ON THE LAST | | | REVISION DOES NOT MATCH THE RISER ON | | | THIS REVISION (GUTTER LOCATION,# OF | | | PANELS,ETC.)YET IS NOT INDICATED AS | | | BEING REVISED (CLOUDED) ON THIS DRAWING. | | | | | | PLEASE CORRECT DRAWINGS TO INDICATE THE | | | REVISIONS MADE AND RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|