| Plan Review Notes For Permit 02011628 |
| Permit Number |
02011628 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-05-14 00:00:00 | *************** UNSAT *************** | | | | | | PLEASE NOTE THAT PLANS ARE COMING BACK | | | WITH THE SOME OF THE SAME COMMENTS FROM | | | THE FIRST TWO REVIEWS NOT ADDRESSED. | | | | | | 1)NOTE: PLEASE NOTE FA/FAC 553-802B WITH | | | RESPECT TO DESIGN PROFESSIONALS DOCUMENT | | | (S). PLANS THAT ARE REJECTED 3 OR MORE | | | TIMES WITH THE SAME COMMENTS ARE SUBJECT | | | TO A FEE OF FOUR TIMES THE AMOUNT OF THE | | | PROPORTION OF THE PERMIT | | | FEE ATTRIBUTED TO PLANS REVIEW. | | | PLEASE NOTE THAT % OF PERMIT FEE IS | | | ABOUT 30%. PLEASE NOTE THAT THIS FEE | | | WILL BE ASSESSED IF CORRECTIONS ARE NOT | | | MADE THIS TIME AROUND. | | | | | | 2)NOTE: PLEASE NOTE CONDUCTORS FOR | | | RISER DIAGRAM STILL DO NOT MEET 240-3-C | | | SEE 75 DEGREE COLUMN/ 110-14. | | | | | | 3)NOTE: PLEASE NOTE THERE IS STILL NO | | | CLARIFICATION FOR EQUIPMENT GROUNDING | | | BETWEEN MAIN DISCONNECT AND PANELS AS | | | ASKED. | | | | | | 4)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | STILL NOTE SHOWN? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. AS PREVIUOUSLY STATED ON FIRST | | | TWO REVIEWS. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. AS OF TODAYS DATE, NO ONE | | | HAS CALLED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|