| 2002-03-25 00:00:00 | ****************** UNSAT *************** |
| | |
| | PLEASE NOTE THAT NOT ALL NOTES FROM |
| | FIRST REVIEW WERE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW LOAD CALCAULTIONS, |
| | NOTHING SHOWN. PLEASE NOTE ALL CONTINUOS |
| | LOADS NEED TO BE SHOWN AT 125%. 215-3, |
| | 230-42 ETC. |
| | |
| | 2)NOTE: PLEASE NOTE THAT UNIT "A" SHOWS |
| | PANEL "H" BEING INSIDE UNIT? PLEASE |
| | CLARIFY IF THIS IS "HOUSE" PANEL AND |
| | WHY IT IS SHOWN IN UNIT"A". GROUPING |
| | MAINS.230-72 |
| | 3)NOTE: PLEASE NOTE THAT PANEL"S" THAT |
| | IS SHOWN FOR STORAGE AREA DOES NOT |
| | CORRELATE ON RISER DIAGRAM. PLEASE NOTE |
| | OTHER METER LOCATION MENTIONS FOR FIRST |
| | FLOOR STORAGE? ARE THESE FOR POSSIBLE |
| | FUTURE TENANT SPACE? |
| | PLEASE NOTE THAT RISER MENTIONS THAT |
| | THERE WILL BE "MCB" PANELS IN THOSE |
| | AREAS, PLEASE NOTE GROUPING OF MAINS |
| | ON PLANS. 230-72 |
| | |
| | 4)NOTE: PLEASE CLARIFY "NUMBER OF |
| | SERVICE DROPS" AS NOTED ON PLANS> PLEASE |
| | NOTE THAT ONLY ONE SERVICE DROP IS |
| | PERMITTED UNDER 230-70. PLEASE CLARIFY |
| | IF THIS NOTE IS MEANT FOR "3" SETS OF |
| | SERVICE ENTRANCE CONDUCTORS.? |
| | |
| | 5)NOTE: PLEASE NOTE THAT MAIN DISCONNECT |
| | FOR PANEL "S" IS SHOWN AS 200A WITH |
| | 150A OCP. PLEASE NOTE THAT CONDUCTORS |
| | TO PANEL ARE ONLY SHOWN AS #6`S?? |
| | 310-16. |
| | |
| | 6)NOTE: PLEASE NOTE THAT SERVICE |
| | ENTRANCE CONDUCTORS ARE SHOWN AS 3 SETS |
| | OF 500MCM. PLEASE NOTE PER 310-16/110-14 |
| | 500MCM IS RATED AT 380A. PLEASE NOTE |
| | 240-3-C. RATED FOR MAIN. |
| | |
| | 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP- |
| | -MENT GROUNDING BETWEEN MAINS AND PANELS |
| | . SIZE PER 250-122 |
| | |
| | 8)NOTE: PLEASE NOTE MISSING MAIN FOR |
| | PANEL"A". 230-72. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |