| Plan Review Notes For Permit 02011628 |
| Permit Number |
02011628 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | 1) PLEASE INDICATE OCCUPANCY TYPES FOR | | | TENANT SPACES A,B,C AND D. | | | 2) PLEASE INDICATE INTERIOR FINISHES | | | FOR WALLS AND CEILINGS. | | | 3) DOORS 200B AND 300B SWING TO FAR INTO | | | THE CORRIDORS 500 AND 600. | | | 4) PLEASE INDICATE ON THE PLANS | | | LOCATIONS OF EMERGENCY LIGHTING | | | EQUIPMENT. | | | 5) MORE DETAILS WILL BE NEEDED WITH | | | REGARDS TO EXITING, STORAGE ARRANGEMENTS | | | SECOND FLOOR AREA OF FUTURE LOW HAZARD | | | STORAGE OCCUPANCY. | | | 6) PLEASE INDICATE ON PLANS IF THE | | | BUILDING IS SPRINKLER PROTECTED OR NOT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|