| 2002-02-06 00:00:00 | ***************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING |
| | NEEDS TO BE SHOWN ON PLANS AND CORRELATE |
| | WITH A PANEL SCHEDULE. |
| | |
| | 2)NOTE: PLEASE NOTE THAT PLANS NEED TO |
| | BE COMPLETE FOR STORAGE AREA AND SECOND |
| | FLOOR. |
| | |
| | 3)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS |
| | AND NOTE THAT "GARAGE" STORAGE NEEDS TO |
| | BE CLARIFIED. |
| | |
| | 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS |
| | WERE SUBMITTED.215-5 |
| | |
| | 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS 3-#10`S TO 150A PANEL? MISPRINT? |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7)NOTE: PLEASE NOTE THAT NO GROUNDING |
| | ELECTRODE SYSTEM IS SHOWN.215-5/250 |
| | |
| | 8)NOTE: PLEASE CLARIFY MAINS NOT SHOWN |
| | FOR FIRST FLOOR AND SECOND FLOOR STORAGE |
| | AREAS.?? PANELS? PLEASE NOTE GROUPING |
| | OF MAINS PER 230-72. |
| | |
| | 9)NOTE: PLEASE NOTE THAT FIRST FLOOR |
| | STORAGE SHOWS ELECTRICAL BUT NO PANEL |
| | |
| | 10)NOTE: PLEASE NOTE MISSING SHOW WINDOW |
| | OUTLETS PER 210-62 |
| | |
| | 11)NOTE: PLEASE NOTE MISSING SIGN PER |
| | 600-5. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |