| 2002-02-13 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | |
| | 1) UNTIL MARCH 1, 2001 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED.NEITHER CODE IS |
| | REFERENCED ON THE PLANS.STATE WHICH |
| | CODE THE WORK IS TO BE CONSTRUCTED TO. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SBC* 1606.4 (FBC 1606.1.4)PRODUCT |
| | APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| | THE NEW STOREFRONTS AND EXTERIOR GLAZED |
| | DOORS 100A, 200A, 300A AND 400A ON |
| | S. DIXIE HWY, AND FOR THE NEW STOREFRONT |
| | LITES ON THE PALM STREET ELEVATION. |
| | |
| | 4) SBC 2405 (FBC 2405)GLAZING IN |
| | HAZARDOUS LOCATIONS.ANNOTATE THE DOOR |
| | SCHEDULE TO SHOW THE REQUIREMENT FOR |
| | TEMPERED, OR ALTERNATIVE SAFETY, GLAZING |
| | IN DOORS 100A, 200A, 300A AND 400A. |
| | |
| | 5) FL ACC CODE 4.22 (FBC 11-4.22) |
| | SHEET A-1, FLOOR PLAN.THE 'TYPICAL |
| | TOILET ROOM' ELEVATIONS DO NOT SHOW |
| | SUFFICIENT DIMENSIONS TO ENSURE |
| | COMPLIANCE WITH FIGURE 29, FOR EXAMPLE, |
| | DISTANCE BETWEEN THE W.C. AND ADJACENT |
| | WALL.ALSO, DOOR 401 IS NOT INCLUDED ON |
| | THE DOOR SCHEDULE. |
| | |
| | 6) FL ACC CODE 4.15 (FBC 11-4.15)AN |
| | ACCESSIBLE DRINKING FOUNTAIN, IN |
| | COMPLIANCE WITH FIGURE 27, SHALL BE |
| | PROVIDED IN EACH TENANT SPACE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |