2002-02-04 00:00:00****************UNSAT!******************
 PLEASE PROVIDE A.I.C. RATING @ FIRST
 MEANS OF DISCONNECT.
 PLEASE INDICATE THE SIZE OF THE SERVICE
 ENTRANCE CONDUCTORS.
 INDICATE THE AMPERAGE RATING OF THE
 METER ENCLOSURE.
 PROVIDE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR.
  
  