| Plan Review Notes For Permit 02011614 |
| Permit Number |
02011614 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-05-17 00:00:00 | WAITING FOR ARCH TO CALL BACK, | | | PLANS NEEDS SOME CORRECTIONS. | | | PLANS STILL SHOW A POOL PANEL AND NOT | | | AS OPT.,ALSO NOT ON RISER. | | | GFI IN BATH NEEDS TO BE MOVED TO CENTER | | | OF SINK. | | | THERE ARE SOME OUTLETS THAT MORETHAN | | | MEET 210-52. IF SHOWN ON PLANS THEN THEY | | | WILL BE REQ`D TO BE INSATLLED, KITCHEN, | | | BED RM. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | | | | ** CALLED ARCH OFFICE AT 6:30AM FRIDAY | | | 5/17/02. LEFT MESSAGE ON VOICE MAIL OF | | | CHARLIE K. |
|