| 2002-04-18 00:00:00 | ****************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE, LOAD CALCUALTIONS |
| | STILL DO NOT CORRELATE WITH NEC ART 220. |
| | |
| | 2)NOTE: PLEASE NOTE THAT POOL PANEL IS |
| | SHOWN ON PANEL SCHEDULE AS 1-POLE 20A |
| | W/ #12. PLEASE NOTE ON RISER AS 30A W/ |
| | #6 AWG. STILL NO NEUTRAL FOR POOL LIGHT? |
| | |
| | 3)NOTE: PLEASE NOTE THAT POOL PUMP IS |
| | SHOWN COMING FROM PANEL IN GARAGE ALSO?? |
| | PLEASE CLARIFY IF POOL PANEL IS EVEN |
| | NEEDED IF EQUIPMENT IS GOING TO BE FED |
| | FROM MAIN PANEL. |
| | |
| | 4)NOTE: PLEASE NOTE 5KW DRYER SHOWN AS |
| | 1-POLE 20A W/#12 AWG??? |
| | |
| | 5)NOTE: PLEASE NOTE THAT CODE FOR |
| | KITCHEN OUTLETS IN NOTES IS STILL REF. |
| | WRONG ART. PLEASE ALSO NOTE MISSING |
| | OUTLET ON KITCHEN COUNTERSPACE PER |
| | 210-52C. THE ART REF FOR KITCHEN IS THE |
| | ART FOR BATHS?? |
| | |
| | 6)NOTE: PLEASE NOTE THAT THE ARC FAULT |
| | PROETCTION FOR BEDROOMS IS STILL NOT |
| | LISTED ON PANEL SCHEDULE. 210-12 |
| | |
| | 7)NOTE: PLEASE NOTE THAT RISER IS SHOW- |
| | -ING 3/0`S FOR 150A SERVICE. PLEASE NOTE |
| | THAT IF 3/0` ARE SHOWN ON PLANS, THEN |
| | THEY WILL BE REQ`D TO BE INSTALLED. THIS |
| | IS JUST A NOTE. 3/0`S CAN STILL BE USED |
| | IF SO DESIRED. |
| | |
| | |
| | |
| | ********* NOTE ********** NOTE******* |
| | PLEASE NOTE THAT THIS IS THE 3RD TIME |
| | THE PLANS HAVE BEEN REVIEWED FOR THIS |
| | MODEL. PLEASE NOTE THAT UNDER THE FLA |
| | ADMINISTRATIVE CODE SEC.553-80. PLANS |
| | REVIEW/DENIED FOR THE SAME ITEMS FOR 3 |
| | OR MORE TIMES ARE SUBJECT TO 4X THE FEE |
| | FOR PLAN REVIEW. |
| | PLEASE NOTE THAT ALL ITEMS NEED TO BE |
| | ADDRESSED. |
| | **************************************** |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |