| 2002-03-21 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 3/04/02: |
| | |
| | 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | THE SITE SPECIFIC SURVEY DRAWING IS NOT |
| | APPLICABLE TO A MASTER MODEL PLAN REVIEW |
| | AND MUST BE REMOVED. |
| | |
| | 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED.THE GENERAL NOTES (SHEET G1) |
| | AND ROOF FRAMING NOTES (SHEET A-05) |
| | STILL REFER TO A BASIC WIND SPEED OF |
| | 110MPH WHICH, UNDER THE 1997 STANDARD |
| | BUILDING CODE, IS BASED ON THE 'FASTEST |
| | MILE'. UNDER 2001 FLORIDA BUILDING CODE, |
| | THE BASIC WIND SPEED FOR THE CITY IS |
| | 140MPH, BASED ON A 3 SECOND GUST.AS A |
| | RESULT OF THIS REVISED METHOD OF |
| | ASSESSING WIND LOAD, THE BASIC VELOCITY |
| | PRESSURES WILL CHANGE.AMEND THE NOTES |
| | TO REFLECT THIS. |
| | |
| | 3) THIS COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED IN RESPECT OF THE MASONRY |
| | COLUMNS ON EACH SIDE OF THE PATIO DOOR |
| | FROM THE LIVING ROOM.SHEET A-02, |
| | FOUNDATION PLAN AND SHEET A-03, FLOOR |
| | PLAN ARE STILL SHOWING DIFFERENT COLUMN |
| | TYPES.AMEND SHEET A-03 TO RECTIFY. |
| | |
| | 12) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | ADD A NOTE TO THE PLANS TO STATE THE |
| | REQUIREMENT FOR HURRICANE IMPACT |
| | SHUTTERS. |
| | |
| | 13) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SUBMIT A PRODUCT APPROVAL FOR THE |
| | GARAGE DOOR. |
| | |
| | 14) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | THE DRAWING SHEETS 1 THROUGH 15 WHICH |
| | SHOULD ACCOMPANY THE GARAGE DOOR PRODUCT |
| | APPROVAL ARE STILL MISSING. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |