| Plan Review Notes For Permit 02011614 |
| Permit Number |
02011614 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-19 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NEED TO BE REDONE, LOAD TAKEN FOR A/C | | | IS MORETHAN 65% AND LOAD TAKEN AFTER | | | FIRST 10,000 IS MORETHAN 40%. | | | PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE NOTE ONLY TWO "HOTS" | | | GOING TO POOL PANEL. NEUTRAL? EQUIPMENT | | | GROUND? 250-122 | | | | | | 3)NOTE: PLEASE NOTE THAT POOL PUMP IS | | | LISTED ON 150A PANEL SCHEDULE, PLEASE | | | LIST THE POOL PANEL AS SHOWN ON RISER | | | DIAGRAM. | | | PLEASE SHOW PANEL LOCATION ON PLANS, | | | EVEN IF OPT. | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | CIRCUITS FOR BEDRROMS. 210-12 | | | | | | 5)NOTE: PLEASE NOTE OUTLET SPACING STILL | | | NEEDS TO MEET 210-52. PLEASE NOTE A FEW | | | MISSING LOCATIONS. | | | | | | 6)NOTE: PLEASE NOTE THAT ART REF FOR | | | KITCHEN CIRCUITS SHOULD BE 210-52B. | | | | | | 7)NOTE: PLEASE CLARIFY TWO A/C | | | DISCONNECTS SHOWN ON RISER DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|