| 2002-03-06 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT RISER SHOWS AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM |
| | METER TO MAIN DISC? PLEASE NOTE THAT |
| | THIS PARALLELING THE NEUTRAL. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING GFI OUTLET |
| | FOR PENINSULAR IN KITCHEN. 210-52-C-3 |
| | |
| | 5)NOTE: PLEASE NOTE MISSING EGRESS LIGHT |
| | -ING IN MANY LOCATIONS. PER 210-70 |
| | PLEASE CLARIFYIF THERE IS AN ATTIC |
| | ACCESS IN MASTER BEDROOM CLOSET? IF YES, |
| | THEN A LT IS REQ`D PER 210-70. |
| | |
| | 6)NOTE: PLEASE NOTE THAT A DEDICATED |
| | CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR |
| | WHIRLPOOL AND LOCATION OF REC IS NOT |
| | SHOWN ON PLANS? PLEASE SHOW. |
| | |
| | 7)NOTE: PLEASE NOTE THAT DERATING OF |
| | A/C AHU HEAT IS TAKEN TWICE AT 65%, |
| | PLEASE NOT ONLY ONE DEDUCTION IS |
| | PERMITTED. |
| | |
| | 8)NOTE: PLEASE NOTE THAT PLANS SHOW |
| | VOLTAGE BEING 120V? PLEASE NOTE THAT |
| | SERVICE SHOULD BE 120/240V. |
| | PLEASE NOTE THAT LOAD SHOWN EXCEEDS |
| | 200A RATING OF PANEL. |
| | |
| | 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTION PER 210-12. LIST ON PANEL |
| | SCHEDULE. |
| | |
| | 10)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | MISSING BLDG/FOOTER STEEL. |
| | |
| | 11)NOTE: PLEASE VERFIY CODE ARTS SHOWN |
| | IN NOTES. PLEASE NOTE THAT BATH ART IS |
| | SHOWN FOR KITCHEN NOTE AND ART FOR BATH |
| | NOTE SHOULD BE 210-11-C-3. |
| | PLEASE CORRELATE.. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |