2002-04-29 00:00:00CHECKLIST:
 1-LOCAL ENGINEER, GORDON F. BUCK IS
 MIXING AND MATCHING DIFFERENT CODES.
 BUILDING WAS NOT DESIGNED BY FBC 2001
 FOR 140 MPH. REVISE ACCORDINGLY.
 2-FRONT PORCH DETAILS AND SPECS SHEET
 WAS NOT SIGNED BY ANYBODY AND WAS NOT
 REVIEWED BY THE AGENCY IN CHARGE OF
 REVIEWING MANUFACTURED HOMES. CLARIFY,
 WHO IS RESPONSIBLE FOR DESIGN AND
 REVIEW OF THESE DRAWINGS?.
 3-PROVIDE HANDRAIL DETAILS AND SPECS AT
 STAIRS. SEC. 1007.5.1(3).
 4-SOIL TEST REPORT ENGINEER'S FAILURE TO
 SIGN, SEAL AND DATE DOCUMENT AS
 REQ'D BY CHAPTER 471 FLORIDA STATUTES.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR MISSILE IMPACT GLAZING.
 6-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK PAID RECEIPT AND STAMPED
 DRAWINGS.