Plan Review Notes
Plan Review Notes For Permit 02011609
Permit Number 02011609
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00*****************UNSAT!*****************
 PLEASE SHOW RISER DIAGRAM COMPLETE WITH
 A.I.C.RATING,GROUNDING,MEANS AND RATING
 OF MAIN DISCONNECT.
 ALSO NOTE THE 4/0 ALUMINUM SHOWN ON PG
 7 OF 25 IS RATED FOR 180 AMPS.
  
 PLEASE PROVIDE THIS INFORMATION AND
 RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392